Our CUMMINS diesel generator set adopt Cummins engines. The Cummins power generator with the world famous alternators---Stamford, Marathon, Leroy-Somer meet your requirements for reliability power quality, rated performance, and efficient operation. It features at low oil consumption, stable performance, easy maintenance, low operation cost, low emission, which are available in sizes ranging from 20kw to 800kw/25kva-1000kva. These clean, modern diesels with optional exhaust after treatment are suitable for either standby/emergency power, continuous or prime power applications.

Cummins Diesel Generator Set Main Features: 
1. High-strength alloy cast iron cylinder body and its head. Quenching crank-shaft,  high strength and smooth operation.
2. Dc24v power start, generator for charging, electronic adjustment system, and its feature is better tan GB/T2820.5&ISO8525-5.
3. PT fuel system (Cummins patent) with unique protect design, low-pressure fuel supply and ultra-high injection pressure (100-140Mp), as well as good atomizing and complete combustion. STC, more complete combustion in higher & lower load. Lower fuel consumption, low pollution exhaust, in compliance to EU2/EU3/EPA/CARB requirements. 6CT PB/W, PN or AD injection pump is used.
4. Valves each cylinder, direct injection, inter cooling technology, utilize advanced exhaust-driven turbocharger, adaptable for high altitude, less than 1500m no loss of output power.
5. The heat-exchanger engine can works well in poor ventilation site, such as basement or antiaircraft tunnel.

Alternator Specification:
1 Alternator brand:
    a) Stamford
    b) Marathon
    c) Leroy-Somer
2 Alternator Features
    a).Brushless, self-exciting, rotary 4-pole magnetic field. AVR(automatic volt regulator)
    b).Single bearing, standard SAE connecting flange and elastic driving sheet. Standard IP21/22/23(or NEMA1) guarding grade.
    c). Rotor silicon-steel lamination dynamic balance is conformance with BS5625, superior lube seals long-life bearing.


Parameters:
1) Rated voltage: 400 / 230V, 220/127V
2) Rated Frequency: 50Hz/60Hz
3) Mode of connection: 3-phase, 4-line
4) Rated power factor: 0.8 (lagging)
5) Wave distortion: <10%
6) Power supply voltage: 24V
7) Voltage fluctuation: <0.5%
8) Voltage / frequency fluctuation: ≤0.5%


Standard Parts:
> Diesel engine
> Brushless alternator
> Control panel
> Heavy duty steel base frame
> Water-cooling system with water tank and fan
> 12/24V starter motor and charging electric motor
> Industrial type silencers, exhaust pipes,
> Flexible exhaust bellows, vibration-damping rubber,
> Lead-acid batteries, connective cables,
> User manual and technical papers 



Optional Features
Fuel System Options
 Low fuel level shutdown
 Engine Oil Heater
 Manual Sump Oil Drain Pump


Exhaust Options
 Exhaust Silencer-industrial(9dB),In-Line
 Exhaust Silencer-Residential (25dB),In-line
 Flexible and fixing kit for industrial silencer
 Flexible and fixing kit for Residential silence

Switchgear
 Circuit Breaker MCCB & ACCB
 Mains auto-charger
 Auto Transfer Switch

Canopy
 Mobile Sets /Trailer
 Weatherproof/Acoustic Enclosures


Voltage Connections
 277/480V,3 Phase
 254/440V,3 Phase
 240/416V,3 Phase
 230/400V,3 Phase
 220/380V,3 Phase
 127/220V,3 Phase
 115/200V,3 Phase
 110/190V,3 Phas

Control Panels
 Earth Fault Relay
 Remote Monitor Interface
 Protection for Alarm Module & Auxiliary Relay
 Parallel control panels

Miscellaneous Options
 Coolant heater-240/120V
 Battery Charger 110-277V,3A
 PCC2100 with barograph
 Earth Fault Relay
 Packing-Export Box
 

Genset Type Power Engine Model Fuel Consump-tion  (L/H) Engine Weight   (kg) Dimension  L*W*H (mm)
  Prime  Kw/Kva Standby Kw/Kva Cylinder Bore        (mm) Stroke        (mm) Displace-ment(L)
HPC22 20/25 22/28 4B3.9-G2 6.7 4L 102 120 3.9 700 1800x730x1260
HPC33 30/48 33/41 4BT3.9-G2 9.3 4L 102 120 3.9 790 1900x730x1260
HPC55 48/60 52/65 4BTA3.9-G2 13.1 4L 102 120 3.9 890 1900x730x1260
HPC90 80/100 90/110 6BT5.9-G2 22 6L 102 120 5.9 1010 2300x800x1300
HPC100 90/110 100/125 6BTA5.9-G2 27 6L 102 120 5.9 1130 2300x800x1300
HPC115 104/130 114/143 6BTAA5.9-G2 30 6L 102 120 5.9 1200 2350X830X1300
HPC160 145/180 160/200 6CTA8.3-G2 40 6L 114 135 8.3 1600 2450X840X1400
HPC180 160/200 180/225 6CTAA8.3-G2 45.4 6L 114 135 8.3 1850 2500X1000X1420
HPC220 200/250 220/275 6LTAA8.9-G2 53 6L 114 145 8.9 2000 2600X1000X1550
HPC275 250/310 275/340 NTA855-G1B 71.4 6L 140 152 14 2600 3000X980X1650
HPC315 280/350 315/394 NTA855-G2A 71.9 6L 140 152 14 2750 3000X980X1650
HPC360 N/A 360/450 NTAA855-G7A 89.2 6L 140 152 14 2900 3200X1200X1800
HPC385 350/440 385/480 KTA19-G3 97 6L 159 159 18.9 3500 3250X1260X2950
HPC440 400/500 440/550 KTA19-G4 101 6L 159 159 18.9 3720 3400X1300X2000
HPC520 N/A 520/650 KTA19-G8 137 6L 159 159 18.9 4250 3600X1500X2100
HPC500 460/575 506/633 KTAA19-G6 127.8 6L 159 159 18.9 4400 3600X1500X2100
HPC660 600/750 660/825 KTA38-G2 167 12V 159 159 37.8 6850 4100X2010X2450
HPC800 720/900 800/1000 KTA38-G2A 191 12V 159 159 37.8 7200 4100X1770X2450
HPC880 800/1000 880/1110 KTA38-G5 209 12V 159 159 37.8 7800 4450X1770X2450
HPC1000 900/1125 1000/1250 KTA38-G9A 221 12V 159 159 38 8500 4350X2010X2450
HPC1100 1000/1250 1100/1375 KTA50-G3 254 16V 159 159 50.3 10000 4800X1860X2450
HPC1320 1200/1500 1320/1650 KTA50-GS8 309 16V 159 159 50.3 12000 5200X2020X2670
HPC1540 1400/1750 1540/1925 QSK60-G3 363 16V 159 190 60.2 15000 6000X2400X2600
HPC1760 1600/2000 1760/2200 QSK60-G4 394 16V 159 190 60.2 15500 6000X2400X2600